Generator kVA ↔ kW Conversion Table

kVA to kW for generators at power factor 0.8: formula, conversion table from 10 to 4,125 kVA, current at 400 V, and the kWm vs kWe difference.

Terex Diesel canopied diesel generator
Contents
  1. The formula
  2. Sizing from a known load
  3. Standby or prime: which kVA?
  4. Engine kW is not generator kW
  5. Common mistakes
  6. kVA → kW conversion table (power factor 0.8)
  7. Load (kW) → required generator size

Generator catalogues give power in kVA, while most loads are listed in kW. A “100 kW generator” and a “100 kVA generator” are therefore two different sets. This page gives the formula, a conversion table for our 10–4,125 kVA range and the current at 400 V.

The formula

Apparent power (kVA) and active power (kW) are linked by the power factor, cos φ. Three-phase diesel generator sets are rated at cos φ = 0.8:

  • kW = kVA × 0.8
  • kVA = kW ÷ 0.8
  • Current at 400 V: I = kVA × 1,000 ÷ (√3 × 400) ≈ 1.44 A per kVA

Example: a 250 kVA set delivers 250 × 0.8 = 200 kW. A 200 kW load needs at least 200 ÷ 0.8 = 250 kVA, and more once motor starting and a reserve are added.

The tables below are calculated with these formulas. The exact standby and prime values of each model are on its own product page, because they depend on the engine and alternator fitted.

Sizing from a known load

If the total running load in kW is known: load ÷ 0.8 = minimum kVA. Then add the starting margin for the largest motor and a reserve of about 20%. A pump or compressor started direct-on-line draws several times its running current while starting, so the start, not the running load, can decide the size. Our power calculator gives a first estimate, and the article on what size generator you need goes through the steps.

Standby or prime: which kVA?

The same set has two ratings. Standby is for supply during mains failures with limited hours per year; prime is for unlimited hours under variable load and is lower. If one offer quotes standby and another quotes prime, you are comparing different sets. See standby, prime and continuous power.

Engine kW is not generator kW

Data sheets often show two kW figures: engine shaft power (kWm) and electrical output of the set (kWe). The engine figure is always higher, because the radiator fan and alternator losses take part of it. Only the electrical output counts when choosing a generator.

Common mistakes

  • Buying “100 kVA” for a 100 kW load. That set gives 80 kW, with no reserve.
  • Comparing engine kW with generator kW. The offers are then not comparable.
  • Ignoring motor starting. The set stalls or the voltage dips when a pump or lift starts.
  • Ignoring site conditions. In heat or at altitude the set delivers less; see derating for temperature and altitude.

Send us your list of loads and we will select the model: contact us.

kVA → kW conversion table (power factor 0.8)

kVAkWCurrent at 400 V (A)Models
10 kVA8 kW≈ 14 A—
20 kVA16 kW≈ 29 A20 kVA
30 kVA24 kW≈ 43 A30 kVA
50 kVA40 kW≈ 72 A50 kVA
75 kVA60 kW≈ 108 A75 kVA
100 kVA80 kW≈ 144 A100 kVA
150 kVA120 kW≈ 217 A150 kVA
200 kVA160 kW≈ 289 A200 kVA
250 kVA200 kW≈ 361 A250 kVA
300 kVA240 kW≈ 433 A—
400 kVA320 kW≈ 577 A400 kVA
500 kVA400 kW≈ 722 A500 kVA
650 kVA520 kW≈ 938 A650 kVA
800 kVA640 kW≈ 1,155 A800 kVA
1,000 kVA800 kW≈ 1,443 A1,000 kVA
1,250 kVA1,000 kW≈ 1,804 A1,250 kVA
1,500 kVA1,200 kW≈ 2,165 A1,500 kVA
2,000 kVA1,600 kW≈ 2,887 A2,000 kVA
2,500 kVA2,000 kW≈ 3,608 A2,500 kVA
3,000 kVA2,400 kW≈ 4,330 A3,000 kVA
4,125 kVA3,300 kW≈ 5,954 A—

kW = kVA × 0.8; I = kVA × 1,000 ÷ (√3 × 400). Calculated values; the exact standby and prime rating of each model is on its product page.

Load (kW) → required generator size

Load (kW)Minimum (kVA)With 20 % reserve (kVA)
10 kW12.515
20 kW2530
40 kW5060
80 kW100120
100 kW125150
150 kW187.5225
200 kW250300
400 kW500600
800 kW1,0001,200
1,600 kW2,0002,400

Motor starting is not included; with large direct-on-line motors the required size can be higher.

Planning a generator for a project?

Send us the power, voltage and destination. We reply with a suitable model, the factory price and the lead time within 24 hours on working days.

Get factory priceAsk on WhatsApp

We reply in English.

Frequently asked questions

How do you convert kVA to kW for a generator?

Three-phase diesel generators are rated at a power factor (cos φ) of 0.8. Multiply kVA by 0.8 to get kW: 100 kVA gives 80 kW, 500 kVA gives 400 kW. To go the other way, divide kW by 0.8.

How many kVA is a 100 kW generator?

100 kW ÷ 0.8 = 125 kVA. If 100 kW is the total load of the site, motor starting currents and a reserve of about 20% are added on top, so in practice a larger set is selected.

Why are generators rated in kVA and not in kW?

The alternator heats up with the total current, not only with the active power. Apparent power in kVA describes that current whatever the type of load, so the alternator and the set are rated in kVA and the kW figure is given at power factor 0.8.

What current does a 100 kVA generator deliver at 400 V?

For a three-phase 400 V system, I = S ÷ (√3 × U) = 100,000 ÷ (1.732 × 400) ≈ 144 A. Cables, circuit breakers and the ATS panel are sized on this current.

Related articles

All articles

Chat on WhatsApp

Download