Generator Sets with Quartz Engines

TRX QZ TA 0038 – 38 kVA Quartz Diesel Generator

Generator set datasheet (PDF)
38 kVA Quartz Diesel Generator – TRX QZ TA 0038 (Canopy)38 kVA Quartz Diesel Generator – TRX QZ TA 0038 (Open type)
Representative image; enclosure and equipment may vary by model.
Standby power38 kVA30.4 kW
Prime power34.2 kVA27.36 kW
Get price and lead timeGet priceTRX QZ TA 0038 Catalogue+90 216 634 34 06
  • Factory-direct sales
  • Delivery from stock available

Service request

Engine
Quartz Q490ZDEngine datasheet on request
Alternator
Terex TA180-24N231.3 kVA · 400 V / 50 Hz · HAlternator datasheet (PDF)
Frequency
50 Hz
Voltage
230/400 V
Warranty
12 months or 1,000 operating hoursTerms for sales outside Türkiye.

TRX QZ TA 0038 is a diesel generator set with 230/400 V / 50 Hz output. Standby power is 38 kVA (30.4 kW) and prime power is 34.2 kVA (27.36 kW). It uses a Quartz Q490ZD engine (4 cylinders, 2.545 L) and a Terex TA180-24N2 alternator. Fuel consumption at 75% load is 6.6 L/h according to manufacturer data.

Summary

TRX QZ TA 0038 is a diesel generator set rated 38 kVA standby and 34.2 kVA prime (30.4 kW / 27.36 kW). It uses a Quartz Q490ZD engine and a Terex TA180-24N2 alternator, with 230/400 V / 50 Hz output. The set is built at our factory in İstanbul, full-load tested before shipment and supplied with a canopy or as an open set.

Key technical data

Standby power38 kVA / 30.4 kW
Prime power34.2 kVA / 27.36 kW
EngineQuartz Q490ZD
AlternatorTerex TA180-24N2
Voltage230/400 V
Frequency50 Hz
Speed1,500 rpm
Fuel consumption (75% load)6.6 L/h
Fuel consumption (100% load)7.2 L/h

Prime and standby ratings

Prime power (34.2 kVA) is the power the set can supply continuously at variable load with no limit on running hours; it is the basis for sites with no grid or an unreliable grid. Standby power (38 kVA) is the maximum power for backup use during a mains failure, for a limited number of hours per year, with no overload allowance. A load that will run continuously should be sized on the prime rating.

Standby, prime and continuous power explained

Typical applications

Shops, offices and small businesses; houses and villas; farms and irrigation; telecom base stations. For correct sizing, send your load list with your quote request.

Engine and alternator options

Models of similar power built with other engine brands:

Production and delivery

The set is built at our factory in İstanbul, where the engine, alternator, base frame, canopy and control panel are assembled, and it is full-load tested before shipment. For export sales the delivery term is EXW İstanbul (Incoterms 2020). The lead time is stated in writing in the quotation, according to the order scope.

Warranty

For sales outside Türkiye the warranty is 12 months or 1,000 operating hours.

Request a quote for this modelAsk on WhatsApp

Frequently asked questions

How many kW does the TRX QZ TA 0038 deliver?

The TRX QZ TA 0038 delivers 30.4 kW (38 kVA) standby and 27.36 kW (34.2 kVA) prime. These are catalogue values at 0.8 power factor and 50 Hz.

Which engine and alternator does the TRX QZ TA 0038 use?

The standard configuration uses a Quartz Q490ZD engine and a Terex TA180-24N2 alternator. If you need another engine brand, we build other models of similar power.

What is the fuel consumption of the TRX QZ TA 0038?

According to catalogue data, fuel consumption is 6.6 L/h at 75% load and 7.2 L/h at 100% load. Actual consumption depends on the load profile and operating conditions.

Can the TRX QZ TA 0038 be built for 60 Hz?

This model can also be built for 60 Hz. 60 Hz ratings depend on the engine, alternator and required voltage (e.g. 480/277 V, 440/254 V, 380/220 V); we quote with project-specific technical data.

What warranty applies to the TRX QZ TA 0038?

For sales outside Türkiye the warranty is 12 months or 1,000 operating hours.

How do I get a quote for the TRX QZ TA 0038?

Fill in the quote form or send the model code on WhatsApp. The quotation is prepared with the delivery country, voltage and frequency, canopy or open-type preference and ATS requirement.

General specifications

Standby power38 kVA / 30.4 kW
Prime power34.2 kVA / 27.36 kW
Voltage230/400 V
Frequency50 Hz
Speed1,500 rpm
Power factor (cos φ)0.8

Engine

MakeQuartz
ModelQ490ZD
Engine type4-stroke diesel
Number of cylinders4
Bore × stroke90 × 100 mm
Displacement2.545 L
AspirationTurbocharged
Fuel injectionDirect injection
Compression ratio17:1
CoolingWater-cooled
GovernorMechanical
Engine net power33 kW
Oil capacity9 L
Coolant capacity20 L

Alternator

MakeTerex
ModelTA180-24N2
Rated output (400 V / 50 Hz, Class H, continuous)31.3 kVA
Alternator standby rating38 kVA
Alternator prime rating34.2 kVA
Voltage230/400 V
Power factor (cos φ)0.8
Number of leads12
Winding pitch2/3
Protection / insulation classIP23/H
ExcitationSelf-excited
AVR modelSX460
Voltage regulation± 1 %
Efficiency85.5 %

Fuel consumption (L/h)

At standby power7.5 L/h
At 100% load7.2 L/h
At 75% load6.6 L/h
At 50% load5 L/h

Dimensions and weight

Open type

Dimensions (L × W × H)1500 × 1000 × 1350 mm
Weight895 kg
Fuel tank125 L

Canopied (soundproof)

Dimensions (L × W × H)2200 × 1000 × 1550 mm
Weight1,045 kg
Fuel tank125 L

Values are for 50 Hz, 230/400 V. For technical data not listed here, see the model catalogue or ask us.

Standard and optional equipment

Standard equipment

  • Digital control panel (engine protection & monitoring)
  • Automatic voltage regulator (AVR)
  • Battery, battery cables and battery charger
  • Industrial-type exhaust silencer
  • Base-frame fuel tank
  • Emergency stop button
  • Anti-vibration mounts
  • Factory load test report
  • Operation and maintenance manual

Optional equipment

  • Automatic transfer switch (ATS)
  • Synchronisation panel (parallel operation)
  • Additional / enlarged fuel tank
  • Silent-type canopy (sound insulated)
  • Trailer chassis
  • Container-type enclosure
  • Remote monitoring module (GSM / IoT)
  • Cold climate package (block heater)
  • Custom colour / corporate identity finish

Standard control panel: Datakom DKG-309. Other controllers are available as options on request (Generator Controllers).

The ATS panel is a separate option, supplied with the set on customer request.

Standard and optional content may vary by model and series.

Request a quote

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

Phone or email (one is enough)

What does your quotation include?

  • Model and configuration The selected model and its configuration: open type or canopy.
  • Standard equipment and control panel The standard equipment list and control panel: Datakom DKG-309 on sets below 500 kVA, Datakom D-500 on sets of 500 kVA and above. Standard control panel (TRX QZ TA 0038): Datakom DKG-309.
  • ATS The ATS panel is a separate option, supplied with the set on customer request.
  • Transport EXW İstanbul; freight quoted separately on request.
  • Warranty 12 months or 1,000 operating hours.
  • Delivery time Stated in writing in the quotation.
  • Payment and delivery terms for export (Incoterms) Agreed in writing at the quotation stage.
Chat on WhatsApp

Download