Uzbekistan – Telecom network sites: 20 kVA prime / 22 kVA standby canopy sets
A written technical specification (telecom network sites) for 20 kVA prime / 22 kVA standby canopy sets: we analysed the requirements and selected TRX QZ TA 0025 (Quartz Q490, 25 kVA standby / 22.5 kVA prime), answered 11 points in a compliance table and prepared the documents listed below.
- Country
- Uzbekistan
- Application
- Telecom network sites
- Power
- 25 kVA standby / 22.5 kVA prime · 50 Hz
- Quantity
- Series supply (many sets)
- Source of requirements
- Written technical specification
Request a quote
Contact us directly
Call +90 216 634 34 06WhatsApp +90 533 582 26 50
We reply in English.
The request
| Rating | 20 kVA prime / 22 kVA standby |
|---|---|
| Electrical | 400/230 V, 50 Hz, 1500 rpm |
| Site conditions | Max 50 °C, min -25 °C |
| Noise | 63 dB(A) |
| Enclosure | Sound-attenuated canopy |
| Fuel tank and autonomy | 250 L tank |
| Automatic transfer switch | Yes |
| Engine | 4 cylinders in-line; 4-stroke; Liquid cooled; Coolant heater; 3 start attempts |
| Alternator | Synchronous brushless with AVR; IP23; Class H; 1 or 3 phases |
| Controller and communications | Mains and generator V/A measurement; 3 configurable analog inputs; 7/7 binary inputs/outputs; Event log 400; Engine hour meter; Built-in web server; GSM/GPRS internet connection; SMS control |
| Other requirements | Standby min 17.6 kW / 22 kVA; Fuel tank heater; Built-in 12 V fuel transfer pump; Fuel filter with water separator; Check valve; 220 V mains battery charger, 12 V system; Low-noise silencers; Spare parts availability min 5 years |
Our work
Requirement analysis · Model selection and sizing
- ≥16 kW / ≥20 kVA prime and ≥22 kVA standby checked → 22 kVA prime / 25 kVA standby model
- 47 technical lines and 11 spare-part lines answered one by one with document references
- Controller datasheet used to close analog/digital I/O, 400 event log, web server, GSM, SMS, scheduler, fuel theft lines
- GSM identified as separate plug-in modem module for the controller
- -25 °C requirement checked against controller rating (-20 °C) → display heater added
- Glow plugs checked: direct-injection engine has none
Point-by-point compliance table
| Item | Required | Our proposal | Assessment |
|---|---|---|---|
| Prime power | 20 kVA prime | 25 kVA standby / 22.5 kVA prime | Complies |
| Frequency and speed | 50 Hz | 50 Hz, 1500 rpm | Complies |
| Enclosure | Sound-attenuated canopy | Canopy, 2200 × 1000 × 1550 mm | Complies |
| Fuel tank | 250 L | 125 L base tank | Deviation / to be confirmed |
| 4 cylinders in-line | – | Manufacturer declaration | Complies |
| 3 start attempts | – | Controller parameter set to 3 | Complies |
| Noise ≤63 dB(A) | – | Manufacturer declaration, critical silencer | Complies |
| -25…+50 °C | – | With controller display heater | Complies |
| 250 L tank, heaters, pump, separator, check valve | – | Included in offered configuration | Complies |
| Spare parts availability 5 years | – | Manufacturer declaration | Complies |
| Glow plugs in spare kit | – | Not applicable to direct-injection engine | Deviation / to be confirmed |
Options identified and priced
- ATS with mains priority
- 250 L base-frame tank
- Fuel tank heater
- Coolant heater
- 12 V fuel transfer pump
- Fuel water separator + check valve
- Controller upgrade with GSM modem
- Controller display heater
- SPTA maintenance kits
Documents prepared · Offer package
- Commercial offer (line-item structure; prices not published here)
- Catalogue pages
- Compliance table
- Manufacturer’s declaration
- Manufacturer’s authorisation letter
- Controller datasheet
Catalogue pages
- Spare parts list with type per item sent
Proposed solution
TRX QZ TA 0025
| Standby power | 25 kVA / 20 kW |
|---|---|
| Prime power | 22.5 kVA / 18 kW |
| Voltage · Frequency · Speed | 230/400 V · 50 Hz · 1,500 rpm |
| Engine | Quartz Q490 · 2.545 L |
| Alternator | Terex TA160-16N2 · AVR SX460 · IP23/H |
| Fuel consumption · At 75% load | 5 L/h |
| Fuel consumption · At 100% load | 6.6 L/h |
| Fuel tank (Canopied (soundproof)) | 125 L |
| Dimensions (L × W × H) (Canopied (soundproof)) | 2,200 × 1,000 × 1,550 mm · 945 kg |
| Dimensions (L × W × H) (Open type) | 1,500 × 1,000 × 1,350 mm · 795 kg |
Values are taken from the model’s datasheet; the full datasheet and catalogue page are on the model page.
Offered configuration
- 250 L base-frame tank with tank heater
- Coolant heater, 12 V fuel transfer pump, fuel water separator, check valve
- Mains battery charger 220 V
- Critical (hospital) type silencer, ≤63 dB(A) (manufacturer declaration)
- −25…+50 °C with controller display heater (manufacturer declaration)
- Electronic speed governor
Packing, shipping and export documents
- Canopy sets are stretch-wrapped with edge protection; loose parts travel in crates or on pallets.
- Export documents: commercial invoice, packing list, certificate of origin, factory test report.
Customer, tender and site names are withheld; only the country is shown. Prices and commercial terms are not published. Customer documents are not shared; requirements are summarised in our own words.
How we work with your specification
- Send the specification, datasheet form or list of needs (PDF, Excel, Word or a message).
- We reply on the same working day and ask about missing or unclear points.
- We size the power (prime/standby), voltage, frequency, ambient conditions and autonomy, select the model and prepare a point-by-point compliance table. Deviations and options are stated openly.
- We send the package — offer, datasheet, catalogue pages and any forms requested; for standard configurations within 24 hours.