Saudi Arabia – 22–50 kVA canopy sets
A request for 22–50 kVA canopy sets: we analysed the requirements and selected TRX P ST 0022 (Perkins 404A-22G1, 22 kVA standby / 20 kVA prime), answered 3 points in a compliance table and prepared the documents listed below.
- Country
- Saudi Arabia
- Power
- 22 kVA standby / 20 kVA prime · 50 Hz
- Quantity
- Series supply (many sets)
- Source of requirements
- Requirements sent by message or e-mail
Request a quote
Contact us directly
Call +90 216 634 34 06WhatsApp +90 533 582 26 50
We reply in English.
The request
| Rating | 5×22, 5×33, 5×50 kVA |
|---|---|
| Enclosure | Sound-attenuated canopy |
| Engine brand | Perkins |
| Alternator | Stamford |
Our work
Requirement analysis · Model selection and sizing
- Three Perkins sizes, 60 Hz 1800 rpm, silent canopy
Point-by-point compliance table
| Item | Required | Our proposal | Assessment |
|---|---|---|---|
| Engine brand | Perkins | Perkins 404A-22G1 | Complies |
| Enclosure | Sound-attenuated canopy | Canopy, 1950 × 900 × 1337 mm | Complies |
| Controller brand | – | DSE / ComAp / SmartGen on request | With option |
Options identified and priced
- Alternative controller brand
Documents prepared · Offer package
- Commercial offer (line-item structure; prices not published here)
- Every set load-tested before shipment
Proposed solution
TRX P ST 0022
| Standby power | 22 kVA / 17.6 kW |
|---|---|
| Prime power | 20 kVA / 16 kW |
| Voltage · Frequency · Speed | 230/400 V · 50 Hz · 1,500 rpm |
| Engine | Perkins 404A-22G1 · 2.216 L |
| Alternator | Stamford S0L2-G1 · AVR SX460 · IP23/H |
| Fuel consumption · At 75% load | 4 L/h |
| Fuel consumption · At 100% load | 5.3 L/h |
| Fuel tank (Canopied (soundproof)) | 82 L |
| Dimensions (L × W × H) (Canopied (soundproof)) | 1,950 × 900 × 1,337 mm · 627 kg |
| Dimensions (L × W × H) (Open type) | 1,600 × 900 × 1,145 mm · 456 kg |
TRX P ST 0033
| Standby power | 33 kVA / 26.4 kW |
|---|---|
| Prime power | 30 kVA / 24 kW |
| Voltage · Frequency · Speed | 230/400 V · 50 Hz · 1,500 rpm |
| Engine | Perkins 1103A-33G · 3.31 L |
| Alternator | Stamford S0L2-P · AVR SX460 · IP23/H |
| Fuel consumption · At 75% load | 5.4 L/h |
| Fuel consumption · At 100% load | 7.1 L/h |
| Fuel tank (Canopied (soundproof)) | 101 L |
| Dimensions (L × W × H) (Canopied (soundproof)) | 2,300 × 1,000 × 1,545 mm · 918 kg |
| Dimensions (L × W × H) (Open type) | 1,900 × 1,000 × 1,396 mm · 708 kg |
TRX P ST 0050
| Standby power | 50 kVA / 40 kW |
|---|---|
| Prime power | 45 kVA / 36 kW |
| Voltage · Frequency · Speed | 230/400 V · 50 Hz · 1,500 rpm |
| Engine | Perkins 1103A-33TG1 · 3.3 L |
| Alternator | Stamford S1L2-N · AVR SX460 · IP23/H |
| Fuel consumption · At 75% load | 8.2 L/h |
| Fuel consumption · At 100% load | 10.7 L/h |
| Fuel tank (Canopied (soundproof)) | 101 L |
| Dimensions (L × W × H) (Canopied (soundproof)) | 2,300 × 1,000 × 1,545 mm · 998 kg |
| Dimensions (L × W × H) (Open type) | 1,900 × 1,000 × 1,396 mm · 788 kg |
Values are taken from the model’s datasheet; the full datasheet and catalogue page are on the model page.
Offered configuration
- 22/20, 33/30, 50/45 kVA standby/prime
- 380/220 V 60 Hz 1800 rpm
- Base fuel tank
- Each set load-tested
Packing, shipping and export documents
- Lead time as stated in the offer: 3–4 weeks from order confirmation.
- Transport: sea freight in containers.
- Canopy sets are stretch-wrapped with edge protection; loose parts travel in crates or on pallets.
- Export documents: commercial invoice, packing list, certificate of origin, factory test report.
Customer, tender and site names are withheld; only the country is shown. Prices and commercial terms are not published. Customer documents are not shared; requirements are summarised in our own words.
How we work with your specification
- Send the specification, datasheet form or list of needs (PDF, Excel, Word or a message).
- We reply on the same working day and ask about missing or unclear points.
- We size the power (prime/standby), voltage, frequency, ambient conditions and autonomy, select the model and prepare a point-by-point compliance table. Deviations and options are stated openly.
- We send the package — offer, datasheet, catalogue pages and any forms requested; for standard configurations within 24 hours.