Latvia – Public tender: 650 kVA prime / 715 kVA standby containerised sets

A written technical specification (public tender) for 650 kVA prime / 715 kVA standby containerised sets: we analysed the requirements and selected TRX SD TA 0725 (SDEC SC27G830D2, 725 kVA standby / 659 kVA prime), answered 14 points in a compliance table and prepared the documents listed below.

Country
Latvia
Application
Public tender
Power
725 kVA standby / 659 kVA prime · 50 Hz
Quantity
Several sets
Source of requirements
Written technical specification

Request a quote

Contact us directly

Call +90 216 634 34 06WhatsApp +90 533 582 26 50

We reply in English.

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

More details? Use the full request form

The request

Rating650 kVA prime / 715 kVA standby
Electrical400/230 V, 50 Hz, 3-phase, 1500 rpm
Site conditionsMax 40 °C, min -30 °C
Noise75 dB(A) at 7 m
EnclosureContainer
Fuel tank and autonomy1,200 L tank, 8 h autonomy at 75 % load
EngineWater-cooled, turbocharged; EN 590 fuel; Fuel consumption ≤95 L/h at 75% and ≤120 L/h at 100% load; Start at -20 °C without pre-heater
AlternatorPMG or AREP excitation; Full damper winding; Class H; IP23; 3-phase sensing AVR ±0.5%; THD <2% no load / ≤4% load
Controller and communicationsGSM + location + history log; Remote start/stop; USB log; Grid-parallel (GPO); Synchronisation/load sharing up to 3 sets; 5 years free monitoring software
StandardsISO 9001:2015; CE; LVD; EMC; 2005/88/EC; 2006/42/EC; IEC 60034-1; ISO 8528-1
Other requirementsLTP ≥715 kVA; 20' ISO 1CC container 6058×2438×2591 mm, silencer ≤+300 mm; 3 compartments, ISO 1161 corner fittings; 16×15 m 185 mm² cables; Gas fire suppression, A1 insulation, panic bars; Cold-climate heaters; Factory noise report (8 points at 7 m) with the bid

Our work

Requirement analysis · Model selection and sizing

  • 650 kVA PRP and LTP ≥715 kVA required → selected 659 kVA prime / 725 kVA standby model
  • Alternative with 700 kVA standby rejected (below 715 kVA LTP)
  • Fuel limits checked: 106.7 L/h at 75% and 141 L/h at 100% vs ≤95 / ≤120 L/h
  • Standard canopy height exceeds 20' ISO container → container layout required

Point-by-point compliance table

ItemRequiredOur proposalAssessment
Prime power650 kVA prime725 kVA standby / 659 kVA primeComplies
Frequency and speed50 Hz50 Hz, 1500 rpmComplies
Fuel tank1,200 L1,263 L base tankComplies
Fuel ≤95 L/h at 75% load––Deviation / to be confirmed
Fuel ≤120 L/h at 100% load––Deviation / to be confirmed
20' ISO 1CC container with hook-lift DIN 30722––Deviation / to be confirmed
3-compartment layout, ≥1,200 L tank–Layout drawing to be confirmedDeviation / to be confirmed
PMG/AREP alternator, AVR ±0.5%––With option
Noise report 8 points at 7 m with bid–Factory test to be performedDeviation / to be confirmed
Negative phase sequence current ≥10%–Alternator manufacturer declaration to be providedDeviation / to be confirmed
Grid parallel and EN 50549 protection–Controller capable; grid requirements to be confirmedDeviation / to be confirmed
-20 °C start without pre-heater–Engine manufacturer confirmation requiredDeviation / to be confirmed
Cold-climate heaters–Cold-climate packageWith option
Trailer registration, cables, handover load test, 72 h replacement set–By bidder; Terex Diesel technical supportBuyer / local scope

Options identified and priced

  • 20' container execution
  • Hook-lift frame
  • PMG + MX321 or AREP + D550 alternator
  • Cold-climate package
  • Stage V engine version
  • 3-axle trailer
  • Spare replacement unit for bidder

Documents prepared · Offer package

  • Compliance table
  • Compliance table prepared with 136 clauses (99 yes, 8 yes-option, 27 to be confirmed, 2 deviations)

Proposed solution

TRX SD TA 0725

Standby power725 kVA / 580 kW
Prime power659 kVA / 527.2 kW
Voltage · Frequency · Speed230/400 V · 50 Hz · 1,500 rpm
EngineSDEC SC27G830D2 · 26.6 L
AlternatorTerex TA355-550N · AVR AS440 · IP23/H
Fuel consumption · At 75% load106.7 L/h
Fuel consumption · At 100% load141 L/h
Fuel tank (Canopied (soundproof))1,263 L
Dimensions (L × W × H) (Canopied (soundproof))4,200 × 1,816 × 2,806 mm · 5,463 kg
Dimensions (L × W × H) (Open type)3,750 × 1,700 × 2,350 mm · 4,635 kg

Values are taken from the model’s datasheet; the full datasheet and catalogue page are on the model page.

Offered configuration

  • Controller: Deep Sea DSE8610 MKII
  • Built into new 20' ISO 1CC container with DIN 30722-1 hook-lift frame
  • ≥1200 L tank in container layout
  • Cold-climate package as option

Packing, shipping and export documents

  • Loading: 20' ISO 1CC on 3-axle trailer
  • Sets are secured on the vehicle or in the container; loose parts travel in crates or on pallets.
  • Export documents: commercial invoice, packing list, certificate of origin, A.TR movement certificate for EU customs clearance, factory test report.

Customer, tender and site names are withheld; only the country is shown. Prices and commercial terms are not published. Customer documents are not shared; requirements are summarised in our own words.

How we work with your specification

  1. Send the specification, datasheet form or list of needs (PDF, Excel, Word or a message).
  2. We reply on the same working day and ask about missing or unclear points.
  3. We size the power (prime/standby), voltage, frequency, ambient conditions and autonomy, select the model and prepare a point-by-point compliance table. Deviations and options are stated openly.
  4. We send the package — offer, datasheet, catalogue pages and any forms requested; for standard configurations within 24 hours.

Send your specification

No specification yet? Download our specification template for a hospital, school or data centre (Word, PDF)

Chat on WhatsApp

Download