United Arab Emirates – 450–660 kVA canopy sets

A request for 450–660 kVA canopy sets: we analysed the requirements and selected TRX P ST 0450 (Perkins 2206A-E13TAG3, 450 kVA standby / 400 kVA prime), answered 1 point in a compliance table and prepared the documents listed below.

Country
United Arab Emirates
Power
450 kVA standby / 400 kVA prime · 50 Hz
Quantity
Several sets
Source of requirements
Requirements sent by message or e-mail

Request a quote

Contact us directly

Call +90 216 634 34 06WhatsApp +90 533 582 26 50

We reply in English.

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

More details? Use the full request form

The request

Rating450 + 660 kVA

Our work

Requirement analysis · Model selection and sizing

  • Two Perkins/Stamford sets at 450 and 660 kVA

Point-by-point compliance table

ItemRequiredOur proposalAssessment
Other engine/alternator brand–Separate quotation on requestWith option

Documents prepared · Offer package

  • Commercial offer (line-item structure; prices not published here)
  • Catalogue pages
  • Factory load-test report (sample)
  • Factory load-test report (sample)Factory load-test report (sample)

Proposed solution

TRX P ST 0450

Standby power450 kVA / 360 kW
Prime power400 kVA / 320 kW
Voltage · Frequency · Speed230/400 V · 50 Hz · 1,500 rpm
EnginePerkins 2206A-E13TAG3 · 12.5 L
AlternatorStamford S4L1D-F · AVR AS440 · IP23/H
Fuel consumption · At 75% load62 L/h
Fuel consumption · At 100% load81 L/h
Fuel tank (Canopied (soundproof))819 L
Dimensions (L × W × H) (Canopied (soundproof))4,050 × 1,600 × 2,615 mm · 3,986 kg
Dimensions (L × W × H) (Open type)3,600 × 1,500 × 2,116 mm · 3,332 kg

TRX P ST 0660

Standby power660 kVA / 528 kW
Prime power600 kVA / 480 kW
Voltage · Frequency · Speed230/400 V · 50 Hz · 1,500 rpm
EnginePerkins 2806A-E18TAG1A · 18.13 L
AlternatorStamford S5L1D-E41 · AVR AS440 · IP23/H
Fuel consumption · At 75% load90 L/h
Fuel consumption · At 100% load123 L/h
Fuel tank (Canopied (soundproof))1,086 L
Dimensions (L × W × H) (Canopied (soundproof))4,000 × 1,816 × 2,925 mm · 5,280 kg
Dimensions (L × W × H) (Open type)3,500 × 1,816 × 2,240 mm · 4,505 kg

Values are taken from the model’s datasheet; the full datasheet and catalogue page are on the model page.

Offered configuration

  • Controller: Deep Sea DSE 7320
  • 450/400 and 660/600 kVA standby/prime
  • 400/230 V 50 Hz
  • Soundproof canopy

Packing, shipping and export documents

  • Transport: road transport by truck.
  • Canopy sets are stretch-wrapped with edge protection; loose parts travel in crates or on pallets.
  • Export documents: commercial invoice, packing list, certificate of origin, factory test report.

Customer, tender and site names are withheld; only the country is shown. Prices and commercial terms are not published. Customer documents are not shared; requirements are summarised in our own words.

How we work with your specification

  1. Send the specification, datasheet form or list of needs (PDF, Excel, Word or a message).
  2. We reply on the same working day and ask about missing or unclear points.
  3. We size the power (prime/standby), voltage, frequency, ambient conditions and autonomy, select the model and prepare a point-by-point compliance table. Deviations and options are stated openly.
  4. We send the package — offer, datasheet, catalogue pages and any forms requested; for standard configurations within 24 hours.

Send your specification

No specification yet? Download our specification template for a hospital, school or data centre (Word, PDF)

Chat on WhatsApp

Download