Burundi – Public tender: 400 kVA canopy set

A written technical specification (public tender) for 400 kVA canopy set: we analysed the requirements and selected TRX P ST 0450 (Perkins 2206A-E13TAG3, 450 kVA standby / 400 kVA prime), answered 5 points in a compliance table and prepared the documents listed below.

Country
Burundi
Application
Public tender
Power
450 kVA standby / 400 kVA prime · 50 Hz
Quantity
1 set
Source of requirements
Written technical specification

Request a quote

Contact us directly

Call +90 216 634 34 06WhatsApp +90 533 582 26 50

We reply in English.

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

More details? Use the full request form

The request

Rating400 kVA
Electrical400/230 V, 50 Hz, 3-phase, 1500 rpm
Noise75 dB(A) at 7 m
EnclosureSound-attenuated canopy
Fuel tank and autonomy8 h autonomy at 75 % load
Engine brandPerkins
EngineEngine model 2206A-E13TAG; Direct injection; Water-cooled; Electronic speed governor; 24 V electric start; Dry-type air filter; Shutdown on low oil pressure, high coolant temp, overspeed
AlternatorBrushless; AVR; Class H; IP23 minimum; Voltage regulation 1%; Efficiency >90%
Controller and communicationsDigital LCD display (V, A, Hz, kW, hours, oil pressure, temp, battery V); Automatic start/stop; Emergency stop
Other requirements320 kW at 0.8 pf; Battery and charger; Silencer; Output circuit breaker min 630 A; Starting cables; User manual; Set of spare filters

Our work

Requirement analysis · Model selection and sizing

  • Requested engine model 2206A-E13TAG matched with 2206A-E13TAG3
  • 400 kVA / 320 kW requirement met by 400 kVA prime / 450 kVA standby set
  • ATS not requested → not included

Point-by-point compliance table

ItemRequiredOur proposalAssessment
Power400 kVA450 kVA standby / 400 kVA primeComplies
Frequency and speed50 Hz50 Hz, 1500 rpmComplies
Engine brandPerkinsPerkins 2206A-E13TAG3Complies
EnclosureSound-attenuated canopyCanopy, 4050 × 1600 × 2615 mmComplies
Perkins 2206A-E13TAG engine–2206A-E13TAG3Complies

Documents prepared · Offer package

  • Commercial offer (line-item structure; prices not published here)
  • Model datasheet
  • Documents with shipment: datasheet, certificate of origin, test report, packing list

Proposed solution

TRX P ST 0450

Standby power450 kVA / 360 kW
Prime power400 kVA / 320 kW
Voltage · Frequency · Speed230/400 V · 50 Hz · 1,500 rpm
EnginePerkins 2206A-E13TAG3 · 12.5 L
AlternatorStamford S4L1D-F · AVR AS440 · IP23/H
Fuel consumption · At 75% load62 L/h
Fuel consumption · At 100% load81 L/h
Fuel tank (Canopied (soundproof))819 L
Dimensions (L × W × H) (Canopied (soundproof))4,050 × 1,600 × 2,615 mm · 3,986 kg
Dimensions (L × W × H) (Open type)3,600 × 1,500 × 2,116 mm · 3,332 kg

Values are taken from the model’s datasheet; the full datasheet and catalogue page are on the model page.

Offered configuration

  • Controller: Deep Sea (DSE) auto-start controller
  • 400/230 V 50 Hz 1500 rpm 3-phase
  • Silent steel powder-coated canopy with base fuel tank
  • Datasheet, certificate of origin, test report supplied

Packing, shipping and export documents

  • Transport: sea freight in containers.
  • Canopy sets are stretch-wrapped with edge protection; loose parts travel in crates or on pallets.
  • Export documents: commercial invoice, packing list, certificate of origin, factory test report.

Customer, tender and site names are withheld; only the country is shown. Prices and commercial terms are not published. Customer documents are not shared; requirements are summarised in our own words.

How we work with your specification

  1. Send the specification, datasheet form or list of needs (PDF, Excel, Word or a message).
  2. We reply on the same working day and ask about missing or unclear points.
  3. We size the power (prime/standby), voltage, frequency, ambient conditions and autonomy, select the model and prepare a point-by-point compliance table. Deviations and options are stated openly.
  4. We send the package — offer, datasheet, catalogue pages and any forms requested; for standard configurations within 24 hours.

Send your specification

No specification yet? Download our specification template for a hospital, school or data centre (Word, PDF)

Chat on WhatsApp

Download