Generator Sets with Cummins Engines

TRX CU LS 0450 – 450 kVA Cummins Diesel Generator

Generator set datasheet (PDF)
450 kVA Cummins Diesel Generator – TRX CU LS 0450 (Canopy)450 kVA Cummins Diesel Generator – TRX CU LS 0450 (Open type)
Representative image; enclosure and equipment may vary by model.
Standby power450 kVA360 kW
Prime power400 kVA320 kW
Get price and lead timeGet priceTRX CU LS 0450 Catalogue+90 216 634 34 06
  • Factory-direct sales
  • 3–4 weeks after order

Service request

Engine
Cummins QSG14-G2
Alternator
Leroy-Somer TAL0473 A
Frequency
50 Hz
Voltage
230/400 V
Warranty
12 months or 1,000 operating hoursTerms for sales outside Türkiye.

TRX CU LS 0450 is a diesel generator set with 230/400 V / 50 Hz output. Standby power is 450 kVA (360 kW) and prime power is 400 kVA (320 kW). It uses a Cummins QSG14-G2 engine (6 cylinders, 11.8 L) and a Leroy-Somer TAL0473 A alternator.

General specifications

Standby power450 kVA / 360 kW
Prime power400 kVA / 320 kW
Voltage230/400 V
Frequency50 Hz
Speed1,500 rpm
Power factor (cos φ)0.8

Engine

MakeCummins
ModelQSG14-G2
Engine type4-stroke diesel
Number of cylinders6
Bore × stroke132 × 144 mm
Displacement11.8 L
AspirationTurbocharged
Fuel injectionDirect injection
CoolingWater-cooled
GovernorElectronic
Oil capacity34.1 L
Coolant capacity48 L

Alternator

MakeLeroy-Somer
ModelTAL0473 A
Alternator standby rating450 kVA
Alternator prime rating400 kVA
Voltage230/400 V
Power factor (cos φ)0.8
Number of leads12
Winding pitch2/3
Protection / insulation classIP23/H
ExcitationSelf-excited
AVR modelAS440
Voltage regulation± 1 %
Efficiency94.3 %

Dimensions and weight

Open type

Weight4,875 kg
Fuel tank1,370 L

Canopied (soundproof)

Weight5,225 kg
Fuel tank1,370 L

Values are for 50 Hz, 230/400 V. For technical data not listed here, see the model catalogue or ask us.

Standard and optional equipment

Standard equipment

  • Digital control panel (engine protection & monitoring)
  • Automatic voltage regulator (AVR)
  • Battery, battery cables and battery charger
  • Industrial-type exhaust silencer
  • Base-frame fuel tank
  • Emergency stop button
  • Anti-vibration mounts
  • Factory load test report
  • Operation and maintenance manual

Optional equipment

  • Automatic transfer switch (ATS)
  • Synchronisation panel (parallel operation)
  • Additional / enlarged fuel tank
  • Silent-type canopy (sound insulated)
  • Trailer chassis
  • Container-type enclosure
  • Remote monitoring module (GSM / IoT)
  • Cold climate package (block heater)
  • Custom colour / corporate identity finish

Standard control panel: Datakom DKG-309. Other controllers are available as options on request (Generator Controllers).

The ATS panel is a separate option, supplied with the set on customer request.

Standard and optional content may vary by model and series.

Request a quote

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

Phone or email (one is enough)

What does your quotation include?

  • Model and configuration The selected model and its configuration: open type or canopy.
  • Standard equipment and control panel The standard equipment list and control panel: Datakom DKG-309 on sets below 500 kVA, Datakom D-500 on sets of 500 kVA and above. Standard control panel (TRX CU LS 0450): Datakom DKG-309.
  • ATS The ATS panel is a separate option, supplied with the set on customer request.
  • Transport EXW İstanbul; freight quoted separately on request.
  • Warranty 12 months or 1,000 operating hours.
  • Delivery time Stated in writing in the quotation.
  • Payment and delivery terms for export (Incoterms) Agreed in writing at the quotation stage.
Chat on WhatsApp

Download