Generator Sets with Perkins Engines

TRX P TA 0033-60 HZ – 37 kVA Perkins Diesel Generator 60 Hz

Generator set datasheet (PDF)

Ratings are for 480/277 V, 60 Hz, 1,800 rpm, cos φ 0.8. 440/254 V, 380/220 V and 220/127 V are available on request; output at these voltages is confirmed in the quote.

37 kVA Perkins Diesel Generator 60 Hz – TRX P TA 0033-60 HZ (Canopy)37 kVA Perkins Diesel Generator 60 Hz – TRX P TA 0033-60 HZ (Open type)
Representative image; enclosure and equipment may vary by model.
Standby power37 kVA29 kW
Prime power35 kVA28 kW
Get price and lead timeGet priceTRX P TA 0033-60 HZ Catalogue+90 216 634 34 06
  • Factory-direct sales
  • 3–4 weeks after order

Service request

Engine
Perkins 1103A-33G
Alternator
Terex TA180-24N237.5 kVA · 480 V / 60 Hz · HAlternator datasheet (PDF)
Frequency
60 Hz
Voltage
277/480 V
Warranty
12 months or 1,000 operating hoursTerms for sales outside Türkiye.

TRX P TA 0033-60 HZ is a diesel generator set with 277/480 V / 60 Hz output. Standby power is 37 kVA (29 kW) and prime power is 35 kVA (28 kW). It uses a Perkins 1103A-33G engine (3 cylinders, 3.31 L) and a Terex TA180-24N2 alternator. Fuel consumption at 75% load is 6.6 L/h according to manufacturer data.

General specifications

Standby power37 kVA / 29 kW
Prime power35 kVA / 28 kW
Voltage277/480 V
Other voltages (on request)254/440 V · 220/380 V · 127/220 V
Frequency60 Hz
Speed1,800 rpm
Power factor (cos φ)0.8

Engine

MakePerkins
Model1103A-33G
Engine type4-stroke diesel
Number of cylinders3
Bore × stroke105 × 127 mm
Displacement3.31 L
AspirationNaturally aspirated
Fuel injectionDirect injection
Compression ratio19.25:1
CoolingWater-cooled
GovernorMechanical
Engine net power32 kW
Engine standby power35 kW
Oil capacity8.3 L
Coolant capacity10.2 L

Alternator

MakeTerex
ModelTA180-24N2
Rated output (480 V / 60 Hz, Class H, continuous)37.5 kVA
Voltage277/480 V
Power factor (cos φ)0.8
Number of leads12
Winding pitch2/3
Protection / insulation classIP23/H
ExcitationSelf-excited
AVR modelSX460
Voltage regulation± 1 %
Efficiency88.1 %

Fuel consumption (L/h)

At standby power9.1 L/h
At 100% load8.6 L/h
At 75% load6.6 L/h
At 50% load4.9 L/h

Dimensions and weight

Open type

Dimensions (L × W × H)1900 × 1000 × 1396 mm
Weight708 kg
Fuel tank101 L

Canopied (soundproof)

Dimensions (L × W × H)2300 × 1000 × 1545 mm
Weight918 kg
Fuel tank101 L

Values are for 60 Hz, 1,800 rpm and 480/277 V (480 V phase-to-phase, 277 V phase-to-neutral; shown as 277/480 V in the table). Rows marked “50 Hz value” are taken from the model’s 50 Hz catalogue; their 60 Hz figures are confirmed in the quote. For technical data not listed here, see the model catalogue or ask us.

Standard and optional equipment

Standard equipment

  • Digital control panel (engine protection & monitoring)
  • Automatic voltage regulator (AVR)
  • Battery, battery cables and battery charger
  • Industrial-type exhaust silencer
  • Base-frame fuel tank
  • Emergency stop button
  • Anti-vibration mounts
  • Factory load test report
  • Operation and maintenance manual

Optional equipment

  • Automatic transfer switch (ATS)
  • Synchronisation panel (parallel operation)
  • Additional / enlarged fuel tank
  • Silent-type canopy (sound insulated)
  • Trailer chassis
  • Container-type enclosure
  • Remote monitoring module (GSM / IoT)
  • Cold climate package (block heater)
  • Custom colour / corporate identity finish

Standard control panel: Datakom DKG-309. Other controllers are available as options on request (Generator Controllers).

The ATS panel is a separate option, supplied with the set on customer request.

Standard and optional content may vary by model and series.

Request a quote

Your request has been received. We will contact you as soon as possible.

Could not send. Please try again or call us. You can also reach us directly: WhatsApp +90 533 582 26 50 · info@terexdiesel.com

Too many submissions in a short time. Please try again in a few minutes.

Phone or email (one is enough)

What does your quotation include?

  • Model and configuration The selected model and its configuration: open type or canopy.
  • Standard equipment and control panel The standard equipment list and control panel: Datakom DKG-309 on sets below 500 kVA, Datakom D-500 on sets of 500 kVA and above. Standard control panel (TRX P TA 0033-60 HZ): Datakom DKG-309.
  • ATS The ATS panel is a separate option, supplied with the set on customer request.
  • Transport EXW İstanbul; freight quoted separately on request.
  • Warranty 12 months or 1,000 operating hours.
  • Delivery time Stated in writing in the quotation.
  • Payment and delivery terms for export (Incoterms) Agreed in writing at the quotation stage.
Chat on WhatsApp

Download