Generator Sets with Perkins Engines
TRX P MC 0110-60 HZ – 120 kVA Perkins Diesel Generator 60 Hz
Generator set datasheet (PDF)Ratings are for 480/277 V, 60 Hz, 1,800 rpm, cos φ 0.8. 440/254 V, 380/220 V and 220/127 V are available on request; output at these voltages is confirmed in the quote.


- Factory-direct sales
- 3–4 weeks after order
- Engine
- Perkins 1104C-44TAG2
- Alternator
- Mecc Alte ECP34-2S/4120 kVA · 480 V / 60 Hz · H
- Frequency
- 60 Hz
- Voltage
- 277/480 V
- Warranty
- 12 months or 1,000 operating hoursTerms for sales outside Türkiye.
TRX P MC 0110-60 HZ is a diesel generator set with 277/480 V / 60 Hz output. Standby power is 120 kVA (96 kW) and prime power is 113 kVA (91 kW). It uses a Perkins 1104C-44TAG2 engine (4 cylinders, 4.4 L) and a Mecc Alte ECP34-2S/4 alternator.
General specifications
| Standby power | 120 kVA / 96 kW |
|---|---|
| Prime power | 113 kVA / 91 kW |
| Voltage | 277/480 V |
| Other voltages (on request) | 254/440 V · 220/380 V · 127/220 V |
| Frequency | 60 Hz |
| Speed | 1,800 rpm |
| Power factor (cos φ) | 0.8 |
Engine
| Make | Perkins |
|---|---|
| Model | 1104C-44TAG2 |
| Engine type | 4-stroke diesel |
| Number of cylinders | 4 |
| Bore × stroke | 105 × 127 mm |
| Displacement | 4.4 L |
| Aspiration | Turbocharged |
| Fuel injection | Direct injection |
| Compression ratio | 18.23:1 |
| Cooling | Water-cooled |
| Governor | Electronic |
| Engine net power | 102 kW |
| Engine standby power | 112 kW |
| Oil capacity | 8 L |
| Coolant capacity | 12.6 L |
Alternator
| Make | Mecc Alte |
|---|---|
| Model | ECP34-2S/4 |
| Rated output (480 V / 60 Hz, Class H, continuous) | 120 kVA |
| Alternator standby rating | 126 kVA |
| Voltage | 277/480 V |
| Power factor (cos φ) | 0.8 |
| Number of leads | 12 |
| Winding pitch | 2/3 |
| Protection / insulation class | IP23/H |
| Excitation | Self-excited |
| AVR model | SX460 |
| Voltage regulation | ± 1 % |
| Efficiency | 93.5 % |
Fuel consumption (L/h)
| At standby power (50 Hz value) | 29.7 L/h |
|---|---|
| At 100% load (50 Hz value) | 26.9 L/h |
| At 75% load (50 Hz value) | 20.2 L/h |
| At 50% load (50 Hz value) | 14.1 L/h |
Dimensions and weight
Open type
| Dimensions (L × W × H) | 2200 × 1000 × 1385 mm |
|---|---|
| Weight | 1,140 kg |
| Fuel tank | 139 L |
Canopied (soundproof)
| Dimensions (L × W × H) | 2600 × 1000 × 1570 mm |
|---|---|
| Weight | 1,365 kg |
| Fuel tank | 139 L |
Values are for 60 Hz, 1,800 rpm and 480/277 V (480 V phase-to-phase, 277 V phase-to-neutral; shown as 277/480 V in the table). Rows marked “50 Hz value” are taken from the model’s 50 Hz catalogue; their 60 Hz figures are confirmed in the quote. For technical data not listed here, see the model catalogue or ask us.
Standard and optional equipment
Standard equipment
- Digital control panel (engine protection & monitoring)
- Automatic voltage regulator (AVR)
- Battery, battery cables and battery charger
- Industrial-type exhaust silencer
- Base-frame fuel tank
- Emergency stop button
- Anti-vibration mounts
- Factory load test report
- Operation and maintenance manual
Optional equipment
- Automatic transfer switch (ATS)
- Synchronisation panel (parallel operation)
- Additional / enlarged fuel tank
- Silent-type canopy (sound insulated)
- Trailer chassis
- Container-type enclosure
- Remote monitoring module (GSM / IoT)
- Cold climate package (block heater)
- Custom colour / corporate identity finish
Standard control panel: Datakom DKG-309. Other controllers are available as options on request (Generator Controllers).
The ATS panel is a separate option, supplied with the set on customer request.
Standard and optional content may vary by model and series.
What does your quotation include?
- Model and configuration The selected model and its configuration: open type or canopy.
- Standard equipment and control panel The standard equipment list and control panel: Datakom DKG-309 on sets below 500 kVA, Datakom D-500 on sets of 500 kVA and above. Standard control panel (TRX P MC 0110-60 HZ): Datakom DKG-309.
- ATS The ATS panel is a separate option, supplied with the set on customer request.
- Transport EXW İstanbul; freight quoted separately on request.
- Warranty 12 months or 1,000 operating hours.
- Delivery time Stated in writing in the quotation.
- Payment and delivery terms for export (Incoterms) Agreed in writing at the quotation stage.